MODEL 471: SINGLE PHASE METER TESTER

The Model 471 is a portable single phase kWh meter tester designed for testing direct connected meters. It is powered from an existing meter supply and contains a variable 30 Ampere current injection circuit, a Digital Signal processor to perform all of necessary voltage, current, power and energy measurements and a separate input and display processor for parameter entry and results display. With inbuilt current and volt- age compensation the Model 471 can achieve an accuracy to 0.05% which makes it ideal for testing any single phase meter.

HARDWARE FEATURES
Power Source

The Model 471 uses the existing service load as a supply to perform single phase meter tests. It has an internal solid state voltage supply which supplies the power required to drive the electronics within the unit.

OPERATING RANGES

  • Measurable Voltage Range (AC)
    – Minimum: 70V
    – Maximum: 270V
  • Selectable Current Ranges (A)
    – 0.1, 0.2, 0.5, 1.0, 1, 2, 3, 5, 10, 15, 30
  • Selectable Power Factor
    – 30 deg Lag: 0.86 PF – 60 deg Lag: 0.5 PF – Unity

ACCURACY

  • Energy measurement accuracy is: 0.05% over the following ranges:
    – 220V to 270V
    -0.5A to 30A
    -0.5PF lag to 1.0PF
    – 48Hz to 52Hz or 58Hz to 62Hz
  • Accuracy of measured parameters
    – Displayed Voltage and Current to 1%. – Frequency to 0.1Hz
    – Phase Angle to 1 deg

RECORDS

500 records may be stored on the Model 471. The operator is able to download the records via USB cable and a communication program to a PC or laptop.

PROTECTION FEATURES

  • Circuit breakers are used for overload protection.
  • LED indicators are used to provide general status infor- mation on the 471.

POWER SUPPLY & CONSUMPTION
Mains Supply 100-270 VAC, 50/60Hz
Power Rating Max 30VA